    Oh right, thanks for that. So fuses in the outlet are pretty typical in the US?

    • ITGuyLevi@programming.dev
      link
      fedilink
      arrow-up
      6
      ·
      6 days ago

      No, we don’t have an actual fuse in the outlet or plug. Some devices have an internal fuse, but not like the UK where almost everything has a fuse in the plug.

    • Rivalarrival@lemmy.today
      link
      fedilink
      English
      arrow-up
      3
      ·
      6 days ago

      No. Our appliance wiring standards basically require every appliance to be able to tolerate a fault current high enough to trip a breaker. We put a 20A cord on a 500mA clock radio. If we get a short inside the appliance, it will draw enough current to trip the breaker.

      The UK allows appliances to have much much lower fault current requirements than their household wiring. They can get away with this by including a current limiter (a fuse) in their plugs.

      We do have provisions for fuses in plugs, but they are typically only used where we would use a lot of very low current wiring: Christmas lighting typically has a tiny fuse in the plug protecting very small wiring.

      • tetris11@feddit.uk
        link
        fedilink
        English
        arrow-up
        1
        ·
        6 days ago

        oh, very interesting – for the clock radio example, wouldn’t the radio fry the circuit board before it tripped the breaker?

        • Rivalarrival@lemmy.today
          link
          fedilink
          English
          arrow-up
          3
          ·
          6 days ago

          It depends on where the fault is. Starting at the input power from the cord, the first component on the circuit board is going to be a factory installed fuse. It’s probably the same on circuit boards made for UK and EU devices because it makes good engineering sense to do it that way, even if the plug is equipped with a fuse. So if the fault is somewhere on the board, it blows the appliance fuse. If it’s somewhere before the appliance fuse, it blows either the plug fuse (if equipped), or the breaker.

        • dondelelcaro@lemmy.world
          link
          fedilink
          arrow-up
          2
          ·
          6 days ago

          Depends on where the short was. If it was a frayed lead in the PSU contacting the neutral, that short might not even hit the board.